Cheshire West and Chester HMO fire safety requirements

Cheshire West and Chester follows the Homestamp standard, which 10 other councils use too.

Is a fire risk assessment needed for the licence?

Expected, but not sent in

The council's guidance talks about fire risk assessments, but it does not ask you to send one with your application. Fire safety law still says you need one.

Who can carry it out?

No rule on who writes it

The council does not say who must carry out the fire risk assessment, so a landlord can do it themselves, as long as it is done properly.

Which standard applies?

Property and Management Standards Applicable to Houses of Multiple Occupation (Amenity Standards)

Published Undated (PDF modified December 2022).

Read the council's document →

When did we last check?

14 October 2026

We re-check every council's documents each month and update this page when they change.

What Cheshire West and Chester expects in 3 typical HMOs

Worked out from the council's own fire safety rules for three common kinds of HMO. Your house may need more or less depending on its layout, which is what a fire risk assessment is for.

2-storey shared house, 5 tenants

Fire alarm system
Grade D2, LD3
Fire doors on bedrooms
Required
Fire door on the kitchen
Required
Protected escape route
Required
Heat detector in the kitchen
Required
Emergency lighting
Not required
Fire blanket in the kitchen
Required
Fire extinguishers
Not required

3-storey shared house, 6 tenants

Fire alarm system
Grade D2, LD3
Fire doors on bedrooms
Required
Fire door on the kitchen
Required
Protected escape route
Required
Heat detector in the kitchen
Required
Emergency lighting
Not required
Fire blanket in the kitchen
Required
Fire extinguishers
Not required

3-storey bedsits with cooking in rooms, 6 tenants

Fire alarm system
Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting
Fire doors on bedrooms
Required
Fire door on the kitchen
Required
Protected escape route
Required
Heat detector in the kitchen
Required
Emergency lighting
Not required
Fire blanket in the kitchen
Required
Fire extinguishers
Not required
  • Grade D2 (mains alarms with a replaceable backup battery)
  • Grade A (a panel system with call points)
  • LD3 (escape route only)
  • LD2 (escape route plus rooms where fires are likely to start)

In the council's own words

The wording these requirements come from, quoted from the published documents.

Fire alarms

Shared regional standard

“A system of mains powered automatic smoke detectors with battery back up, to achieve a Grade D system in accordance with the current BS 5839 Part 6 (or equivalent), must be installed. ... In kitchens a heat detector, rather than a smoke detector, must be installed. ... By providing a detector/ sounder in the communal areas ... Detectors must be sited in all areas containing a fire risk. ... The main system shall provide heat detectors in individual lets and smoke detectors in common areas and any storerooms/cellars (interlinked system). ... single point smoke alarms are also required. These detectors are not interlinked between rooms. ... GRADE A of the current BS 5859 Part 6 (or equivalent). Automatic detection must provide LD2 coverage. ... comprising of GRADE A (main system) and GRADE D (Single point smoke alarms). The main system must provide LD2 coverage.”
A Guide to Fire and Security Protection in Multi-Occupied Residential Properties (Homestamp Consortium), Revision 2015

Fire doors

Council's own standard

“A protected means of escape is generally required with Fire doors (FD30s) on all bedrooms, living rooms and kitchens that lead onto the hall stairs and landing.”
Property and Management Standards Applicable to Houses of Multiple Occupation (Amenity Standards), Cheshire West and Chester Council, Undated (PDF modified December 2022)

Escape route

Council's own standard

“A protected means of escape is generally required with Fire doors (FD30s) on all bedrooms, living rooms and kitchens that lead onto the hall stairs and landing.”
Property and Management Standards Applicable to Houses of Multiple Occupation (Amenity Standards), Cheshire West and Chester Council, Undated (PDF modified December 2022)

Kitchen heat detector

LACORS national guide

“additional interlinked heat alarm with integral battery back-up located in the kitchen”
LACORS Housing - Fire Safety: guidance on fire safety provisions for certain types of existing housing, July 2008

Emergency lighting

Shared regional standard

“Subject to a fire risk assessment emergency lighting should not be necessary, provided that the escape route is not long or complex and there is effective artificial or borrowed lighting. ... Where emergency lighting is considered to be necessary, it should be provided in accordance with the current BS 5266 Part 1 (or equivalent) to cover the protected escape route.”
A Guide to Fire and Security Protection in Multi-Occupied Residential Properties (Homestamp Consortium), Revision 2015

Fire extinguishers

Shared regional standard

“Landlords should consider the following points where extinguishers are to be provided ... devices. Unless a fire is very small, it is best ... on balance to encourage people simply to”
A Guide to Fire and Security Protection in Multi-Occupied Residential Properties (Homestamp Consortium), Revision 2015

Spotted something out of date? Tell us and we will check it.

Common questions

Do I need a fire risk assessment for a Cheshire West and Chester HMO licence?
The council's guidance talks about fire risk assessments, but it does not ask you to send one with your application. Fire safety law still says you need one.
Can I do my own HMO fire risk assessment in Cheshire West and Chester?
The council does not say who must carry out the fire risk assessment, so a landlord can do it themselves, as long as it is done properly.
Which fire safety standard does Cheshire West and Chester use for HMOs?
Cheshire West and Chester follows LACORS, the national guide on fire safety in existing housing.
What fire alarm does a 3-storey shared house need in Cheshire West and Chester?
For a typical 3-storey shared house with 6 tenants, Cheshire West and Chester's rules work out at Grade D2, LD3. Your house may need something different depending on its layout, so check it properly with a fire risk assessment.

Check your Cheshire West and Chester HMO against the council's standard

Answer plain-English questions about your house and get a fire risk assessment report built on Cheshire West and Chester's rules. £45, no subscription.