Cheshire East HMO fire safety requirements

Cheshire East publishes its own HMO fire safety standard, "Amenities and Facilities Standards in Houses in Multiple Occupation (HMOs): Guidance for Landlords and Agents" (Version 2.0, November 2020). It is based on the Homestamp standard, which 10 other councils use too.

Is a fire risk assessment needed for the licence?

Expected, but not sent in

The council's guidance talks about fire risk assessments, but it does not ask you to send one with your application. Fire safety law still says you need one.

Who can carry it out?

No rule on who writes it

The council does not say who must carry out the fire risk assessment, so a landlord can do it themselves, as long as it is done properly.

Which standard applies?

Amenities and Facilities Standards in Houses in Multiple Occupation (HMOs): Guidance for Landlords and Agents

Published Version 2.0, November 2020.

Read the council's document →

When did we last check?

14 October 2026

We re-check every council's documents each month and update this page when they change.

What Cheshire East expects in 3 typical HMOs

Worked out from the council's own fire safety rules for three common kinds of HMO. Your house may need more or less depending on its layout, which is what a fire risk assessment is for.

2-storey shared house, 5 tenants

Fire alarm system
Grade D1, LD3
Fire doors on bedrooms
Not required
Fire door on the kitchen
Not required
Protected escape route
Not required
Heat detector in the kitchen
Required
Emergency lighting
Required
Fire blanket in the kitchen
Required
Fire extinguishers
Not required

3-storey shared house, 6 tenants

Fire alarm system
Grade D1, LD3
Fire doors on bedrooms
Required
Fire door on the kitchen
Required
Protected escape route
Required
Heat detector in the kitchen
Required
Emergency lighting
Required
Fire blanket in the kitchen
Required
Fire extinguishers
Not required

3-storey bedsits with cooking in rooms, 6 tenants

Fire alarm system
Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting
Fire doors on bedrooms
Required
Fire door on the kitchen
Required
Protected escape route
Required
Heat detector in the kitchen
Required
Emergency lighting
Required
Fire blanket in the kitchen
Required
Fire extinguishers
Not required
  • Grade D1 (mains alarms with a sealed backup battery)
  • Grade A (a panel system with call points)
  • LD3 (escape route only)
  • LD2 (escape route plus rooms where fires are likely to start)

In the council's own words

The wording these requirements come from, quoted from the published documents.

Fire alarms

Council's own standard

“The table below provides some examples of typical property types and the fire precautions that would be appropriate. ... Interlinked mains wired smoke detectors with battery back-up ... Interlinked mains wired heat detector with battery back-up in ... 3 or 4 Storey Shared ... 30 minute fire resisting construction throughout the ... 3 or 4 Storey Bedsit ... Control panel required ... Mains wired smoke detectors with battery back-up located in ... each bedsit, linked to the control panel ... Mains wired heat detectors with battery back-up located in each ... Mains wired smoke detectors with battery back-up, non- interlinked, located in each bedsit.”
Amenities and Facilities Standards in Houses in Multiple Occupation (HMOs): Guidance for Landlords and Agents (Cheshire East Council), Version 2.0, November 2020

Fire doors

LACORS national guide

“30-minute protected route note 8, is required, including 30-minute fire-resisting construction and FD30 doors to all risk rooms (without smoke seals ... 30-minute fire-resisting construction and FD30S doors to all risk rooms. Travel distance must not be excessive”
LACORS Housing - Fire Safety: guidance on fire safety provisions for certain types of existing housing, July 2008

Escape route

LACORS national guide

“No requirement for full 30-minute protected route note 7, but the escape route should have sound, traditional construction and should not pass through risk rooms ... 30-minute protected route note 8, is required, including 30-minute fire-resisting construction”
LACORS Housing - Fire Safety: guidance on fire safety provisions for certain types of existing housing, July 2008

Kitchen heat detector

LACORS national guide

“additional interlinked heat alarm with integral battery back-up located in the kitchen”
LACORS Housing - Fire Safety: guidance on fire safety provisions for certain types of existing housing, July 2008

Emergency lighting

Council's own standard

“Fire safety measures required by Cheshire East will typically require: ... An Emergency Lighting system conforming to BS5266; Part 1”
Amenities and Facilities Standards in Houses in Multiple Occupation (HMOs): Guidance for Landlords and Agents (Cheshire East Council), Version 2.0, November 2020

Fire extinguishers

Shared regional standard

“Landlords should consider the following points where extinguishers are to be provided ... devices. Unless a fire is very small, it is best ... on balance to encourage people simply to”
A Guide to Fire and Security Protection in Multi-Occupied Residential Properties (Homestamp Consortium), Revision 2015

Spotted something out of date? Tell us and we will check it.

Common questions

Do I need a fire risk assessment for a Cheshire East HMO licence?
The council's guidance talks about fire risk assessments, but it does not ask you to send one with your application. Fire safety law still says you need one.
Can I do my own HMO fire risk assessment in Cheshire East?
The council does not say who must carry out the fire risk assessment, so a landlord can do it themselves, as long as it is done properly.
Which fire safety standard does Cheshire East use for HMOs?
Cheshire East publishes "Amenities and Facilities Standards in Houses in Multiple Occupation (HMOs): Guidance for Landlords and Agents" (Version 2.0, November 2020).
What fire alarm does a 3-storey shared house need in Cheshire East?
For a typical 3-storey shared house with 6 tenants, Cheshire East's rules work out at Grade D1, LD3. Your house may need something different depending on its layout, so check it properly with a fire risk assessment.