Used by 2 councils
Adur and Worthing HMO fire safety standards
Adur and Worthing councils publish one Compliance Guide for Houses in Multiple Occupation (V1.4, 2023), which sets out the fire safety they expect in an HMO.
Read "Compliance Guide for Houses in Multiple Occupation (HMOs)" (V1.4 2023) →What the Adur and Worthing standard expects in 3 typical HMOs
Your council may have changed some of the detail, so check your council's own page below.
| Requirement | 2-storey shared house, 5 tenants | 3-storey shared house, 6 tenants | 3-storey bedsits with cooking in rooms, 6 tenants |
|---|---|---|---|
| Fire alarm system | Grade D2, LD3 | Grade D2, LD3 | Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting |
| Fire doors on bedrooms | Required | Required | Required |
| Fire door on the kitchen | Required | Required | Required |
| Protected escape route | Required | Required | Required |
| Heat detector in the kitchen | Required | Required | Required |
| Emergency lighting | Not required | Not required | Not required |
| Fire blanket in the kitchen | Required | Required | Required |
| Fire extinguishers | Not required | Not required | Not required |
- Grade D2 (mains alarms with a replaceable backup battery)
- Grade A (a panel system with call points)
- LD3 (escape route only)
- LD2 (escape route plus rooms where fires are likely to start)
What the standard says
Fire doors
Shared regional standard
“A key element of the protected route is the doors that open on to the route from risk rooms. In most cases you will require a 30 minute fire rated door set, either an FD30S door set, or an FD30 door set.”
Escape route
Shared regional standard
“You will be required to create a protected route out of the property from all habitable rooms. This will normally be a 30 minute protected route (to allow at least 30 minutes for occupants to be alerted to a fire and escape without harm)”
Fire extinguishers
Shared regional standard
“You are not required to provide fire extinguishers for residents to use, but in some cases there may be an organisational requirement to have them i.e. if you have staff on site.”
Common questions
Which councils use the Adur and Worthing standard?
2 councils: Adur, Worthing.
Is the Adur and Worthing standard stricter than LACORS?
In some places, yes. Where it asks for more than LACORS, you need to meet it. Where it asks for less, or says nothing, we use the LACORS minimum instead.