West Lindsey HMO fire safety requirements
West Lindsey publishes its own HMO fire safety standard, "Houses in Multiple Occupation Standards (West Lindsey District Council)" (January 2019).
Is a fire risk assessment needed for the licence?
Yes, with your licence application
The council lists a written fire risk assessment as one of the documents you send with your HMO licence application.
Who can carry it out?
No rule on who writes it
The council does not say who must carry out the fire risk assessment, so a landlord can do it themselves, as long as it is done properly.
Which standard applies?
Houses in Multiple Occupation Standards (West Lindsey District Council)
Published January 2019.
Read the council's document →When did we last check?
14 October 2026
We re-check every council's documents each month and update this page when they change.
What West Lindsey expects in 3 typical HMOs
Worked out from the council's own fire safety rules for three common kinds of HMO. Your house may need more or less depending on its layout, which is what a fire risk assessment is for.
2-storey shared house, 5 tenants
- Fire alarm system
- Grade D2, LD3
- Fire doors on bedrooms
- Not required
- Fire door on the kitchen
- Not required
- Protected escape route
- Not required
- Heat detector in the kitchen
- Required
- Emergency lighting
- Not required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
3-storey shared house, 6 tenants
- Fire alarm system
- Grade D2, LD3
- Fire doors on bedrooms
- Required*
- Fire door on the kitchen
- Required*
- Protected escape route
- Required*
- Heat detector in the kitchen
- Required
- Emergency lighting
- Not required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
3-storey bedsits with cooking in rooms, 6 tenants
- Fire alarm system
- Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting
- Fire doors on bedrooms
- Required
- Fire door on the kitchen
- Required
- Protected escape route
- Required
- Heat detector in the kitchen
- Required
- Emergency lighting
- Required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
| Requirement | 2-storey shared house, 5 tenants | 3-storey shared house, 6 tenants | 3-storey bedsits with cooking in rooms, 6 tenants |
|---|---|---|---|
| Fire alarm system | Grade D2, LD3 | Grade D2, LD3 | Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting |
| Fire doors on bedrooms | Not required | Required* | Required |
| Fire door on the kitchen | Not required | Required* | Required |
| Protected escape route | Not required | Required* | Required |
| Heat detector in the kitchen | Required | Required | Required |
| Emergency lighting | Not required | Not required | Required |
| Fire blanket in the kitchen | Required | Required | Required |
| Fire extinguishers | Recommended | Recommended | Recommended |
- Grade D2 (mains alarms with a replaceable backup battery)
- Grade A (a panel system with call points)
- LD3 (escape route only)
- LD2 (escape route plus rooms where fires are likely to start)
- * The council's own standard asks for less here, so we show the LACORS minimum. We never go below LACORS.
In the council's own words
The wording these requirements come from, quoted from the published documents.
Fire alarms
LACORS national guide
“Shared house HMO of three or four storeys (shared cooking facilities) Grade D: LD3 coverage + additional detection to the kitchen, lounge and any cellar containing a risk (interlinked) Shared house HMO of five or six storeys (shared cooking facilities) Grade A: LD2 coverage ... Bedsit HMO of one or two storeys with individual cooking facilities within bedsits A mixed system: Grade D: LD2 coverage in the common areas and heat detectors in bedsits (interlinked) Grade D smoke alarm in each bedsit to protect the sleeping occupants (non-interlinked) Bedsit HMO of three to six storeys with individual cooking facilities within bedsits A mixed system: Grade A: LD2 coverage in the common areas ... Where cooking facilities are sited in shared kitchen, not within bedsits: interlinked smoke alarms with integral battery backup located in each bedsit”
Fire doors
Council's own standard
“Sound, well-constructed and close fitting, conventional doors required”
Escape route
Council's own standard
“Sound, well-constructed and close fitting, conventional doors required”
Kitchen heat detector
LACORS national guide
“additional interlinked heat alarm with integral battery back-up located in the kitchen”
Emergency lighting
Council's own standard
“Grade A, LD2 system Smoke detectors located throughout the escape route ... Emergency escape lighting required Conventional artificial lighting required Firefighting Fire blanket to be provided in each bedsit within cooking”
Fire extinguishers
LACORS national guide
“a simple multi-purpose extinguisher is recommended on each floor in the common parts of HMOs and buildings containing flats.”
Spotted something out of date? Tell us and we will check it.
Not in West Lindsey?
Common questions
Do I need a fire risk assessment for a West Lindsey HMO licence?
Can I do my own HMO fire risk assessment in West Lindsey?
Which fire safety standard does West Lindsey use for HMOs?
What fire alarm does a 3-storey shared house need in West Lindsey?
Check your West Lindsey HMO against the council's standard
Answer plain-English questions about your house and get a fire risk assessment report built on West Lindsey's rules. £45, no subscription.