Yorkshire and The Humber
Wakefield HMO fire safety requirements
Wakefield does not publish a fire safety standard of its own. It points landlords to LACORS, the national guide on fire safety in existing housing, so that is what applies to your HMO.
Is a fire risk assessment needed for the licence?
Expected, but not sent in
The council's guidance talks about fire risk assessments, but it does not ask you to send one with your application. Fire safety law still says you need one.
Who can carry it out?
No rule on who writes it
The council does not say who must carry out the fire risk assessment, so a landlord can do it themselves, as long as it is done properly.
Which standard applies?
Wakefield Council's Adopted Standards for HMOs
Published 2018.
Read the council's document →When did we last check?
14 October 2026
We re-check every council's documents each month and update this page when they change.
What Wakefield expects in 3 typical HMOs
Worked out from the council's own fire safety rules for three common kinds of HMO. Your house may need more or less depending on its layout, which is what a fire risk assessment is for.
2-storey shared house, 5 tenants
- Fire alarm system
- Grade D2, LD3
- Fire doors on bedrooms
- Required
- Fire door on the kitchen
- Required
- Protected escape route
- Required
- Heat detector in the kitchen
- Required
- Emergency lighting
- Not required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
3-storey shared house, 6 tenants
- Fire alarm system
- Grade D2, LD3
- Fire doors on bedrooms
- Required
- Fire door on the kitchen
- Required
- Protected escape route
- Required
- Heat detector in the kitchen
- Required
- Emergency lighting
- Not required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
3-storey bedsits with cooking in rooms, 6 tenants
- Fire alarm system
- Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting
- Fire doors on bedrooms
- Required
- Fire door on the kitchen
- Required
- Protected escape route
- Required
- Heat detector in the kitchen
- Required
- Emergency lighting
- Not required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
| Requirement | 2-storey shared house, 5 tenants | 3-storey shared house, 6 tenants | 3-storey bedsits with cooking in rooms, 6 tenants |
|---|---|---|---|
| Fire alarm system | Grade D2, LD3 | Grade D2, LD3 | Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting |
| Fire doors on bedrooms | Required | Required | Required |
| Fire door on the kitchen | Required | Required | Required |
| Protected escape route | Required | Required | Required |
| Heat detector in the kitchen | Required | Required | Required |
| Emergency lighting | Not required | Not required | Not required |
| Fire blanket in the kitchen | Required | Required | Required |
| Fire extinguishers | Recommended | Recommended | Recommended |
- Grade D2 (mains alarms with a replaceable backup battery)
- Grade A (a panel system with call points)
- LD3 (escape route only)
- LD2 (escape route plus rooms where fires are likely to start)
In the council's own words
The wording these requirements come from, quoted from the published documents.
Fire alarms
LACORS national guide
“Shared house HMO of three or four storeys (shared cooking facilities) Grade D: LD3 coverage + additional detection to the kitchen, lounge and any cellar containing a risk (interlinked) Shared house HMO of five or six storeys (shared cooking facilities) Grade A: LD2 coverage ... Bedsit HMO of one or two storeys with individual cooking facilities within bedsits A mixed system: Grade D: LD2 coverage in the common areas and heat detectors in bedsits (interlinked) Grade D smoke alarm in each bedsit to protect the sleeping occupants (non-interlinked) Bedsit HMO of three to six storeys with individual cooking facilities within bedsits A mixed system: Grade A: LD2 coverage in the common areas ... Where cooking facilities are sited in shared kitchen, not within bedsits: interlinked smoke alarms with integral battery backup located in each bedsit”
Fire doors
Council's own standard
“Fire doors will be required to protect the main means of escape, mainly the stairway, from the top floor through to the front external door”
Escape route
Council's own standard
“Fire doors will be required to protect the main means of escape, mainly the stairway, from the top floor through to the front external door”
Kitchen heat detector
LACORS national guide
“additional interlinked heat alarm with integral battery back-up located in the kitchen”
Emergency lighting
LACORS national guide
“Emergency escape lighting required only if the route is long or complex or where there is no effective borrowed light ... Shared house HMO of five or six storeys (shared cooking facilities) Conventional lighting and emergency escape lighting”
Fire extinguishers
LACORS national guide
“a simple multi-purpose extinguisher is recommended on each floor in the common parts of HMOs and buildings containing flats.”
Spotted something out of date? Tell us and we will check it.
Common questions
Do I need a fire risk assessment for a Wakefield HMO licence?
Can I do my own HMO fire risk assessment in Wakefield?
Which fire safety standard does Wakefield use for HMOs?
What fire alarm does a 3-storey shared house need in Wakefield?
Check your Wakefield HMO against the council's standard
Answer plain-English questions about your house and get a fire risk assessment report built on Wakefield's rules. £45, no subscription.