Stroud HMO fire safety requirements

Stroud publishes its own HMO fire safety standard, "Local Authority Standards for Licensed Houses in Multiple Occupation (HMO's) Under Part 2 Housing Act 2004 (Stroud District Council)" (Not dated).

Is a fire risk assessment needed for the licence?

Yes, with your licence application

The council lists a written fire risk assessment as one of the documents you send with your HMO licence application.

Who can carry it out?

A "competent person"

The council says a "competent person" must carry it out. In fire safety law that means someone with enough training, experience or knowledge to assess the house properly. A careful landlord can meet that.

Which standard applies?

Local Authority Standards for Licensed Houses in Multiple Occupation (HMO's) Under Part 2 Housing Act 2004 (Stroud District Council)

Published Not dated.

Read the council's document →

When did we last check?

14 October 2026

We re-check every council's documents each month and update this page when they change.

What Stroud expects in 3 typical HMOs

Worked out from the council's own fire safety rules for three common kinds of HMO. Your house may need more or less depending on its layout, which is what a fire risk assessment is for.

2-storey shared house, 5 tenants

Fire alarm system
Grade D2, LD3
Fire doors on bedrooms
Not required
Fire door on the kitchen
Not required
Protected escape route
Not required
Heat detector in the kitchen
Required
Emergency lighting
Not required
Fire blanket in the kitchen
Required
Fire extinguishers
Recommended

3-storey shared house, 6 tenants

Fire alarm system
Grade D2, LD3
Fire doors on bedrooms
Required
Fire door on the kitchen
Required
Protected escape route
Required
Heat detector in the kitchen
Required
Emergency lighting
Required
Fire blanket in the kitchen
Required
Fire extinguishers
Recommended

3-storey bedsits with cooking in rooms, 6 tenants

Fire alarm system
Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting
Fire doors on bedrooms
Required
Fire door on the kitchen
Required
Protected escape route
Required
Heat detector in the kitchen
Required
Emergency lighting
Required
Fire blanket in the kitchen
Required
Fire extinguishers
Recommended
  • Grade D2 (mains alarms with a replaceable backup battery)
  • Grade A (a panel system with call points)
  • LD3 (escape route only)
  • LD2 (escape route plus rooms where fires are likely to start)

In the council's own words

The wording these requirements come from, quoted from the published documents.

Fire alarms

Council's own standard

“A Category LD3 Grade A or D fire detection system conforming to BS5839: Part 6:2013 (a Grade A system will ... be required for properties occupied by 7 or more persons). The system will normally include interlinked smoke ... any cellar. Grade D detectors should have integral battery back-up. ... For 5 and 6 storey properties a Category LD2 Grade A system will be required. ... A Category LD2 Grade A or D fire detection system conforming to BS5839: Part 6:2013 (a Grade A system will ... be required for properties occupied by 7 or more persons and 3 or more storey properties). ... An additional Grade D non-interlinked smoke detector with integral battery back-up will”
Local Authority Standards for Licensed Houses in Multiple Occupation (HMO's) Under Part 2 Housing Act 2004 (Stroud District Council), Not dated

Fire doors

LACORS national guide

“30-minute protected route note 8, is required, including 30-minute fire-resisting construction and FD30 doors to all risk rooms (without smoke seals ... 30-minute fire-resisting construction and FD30S doors to all risk rooms. Travel distance must not be excessive”
LACORS Housing - Fire Safety: guidance on fire safety provisions for certain types of existing housing, July 2008

Escape route

LACORS national guide

“No requirement for full 30-minute protected route note 7, but the escape route should have sound, traditional construction and should not pass through risk rooms ... 30-minute protected route note 8, is required, including 30-minute fire-resisting construction”
LACORS Housing - Fire Safety: guidance on fire safety provisions for certain types of existing housing, July 2008

Kitchen heat detector

LACORS national guide

“additional interlinked heat alarm with integral battery back-up located in the kitchen”
LACORS Housing - Fire Safety: guidance on fire safety provisions for certain types of existing housing, July 2008

Emergency lighting

Council's own standard

“Emergency lighting (3 and 4 An emergency lighting system to BS 5266:1:2011. ... storey HMOs)”
Local Authority Standards for Licensed Houses in Multiple Occupation (HMO's) Under Part 2 Housing Act 2004 (Stroud District Council), Not dated

Fire extinguishers

LACORS national guide

“a simple multi-purpose extinguisher is recommended on each floor in the common parts of HMOs and buildings containing flats.”
LACORS Housing - Fire Safety: guidance on fire safety provisions for certain types of existing housing, July 2008

Spotted something out of date? Tell us and we will check it.

Common questions

Do I need a fire risk assessment for a Stroud HMO licence?
The council lists a written fire risk assessment as one of the documents you send with your HMO licence application.
Can I do my own HMO fire risk assessment in Stroud?
The council says a "competent person" must carry it out. In fire safety law that means someone with enough training, experience or knowledge to assess the house properly. A careful landlord can meet that.
Which fire safety standard does Stroud use for HMOs?
Stroud publishes "Local Authority Standards for Licensed Houses in Multiple Occupation (HMO's) Under Part 2 Housing Act 2004 (Stroud District Council)" (Not dated). Like most councils, it builds on the national LACORS guide.
What fire alarm does a 3-storey shared house need in Stroud?
For a typical 3-storey shared house with 6 tenants, Stroud's rules work out at Grade D2, LD3. Your house may need something different depending on its layout, so check it properly with a fire risk assessment.

Check your Stroud HMO against the council's standard