Stroud HMO fire safety requirements
Stroud publishes its own HMO fire safety standard, "Local Authority Standards for Licensed Houses in Multiple Occupation (HMO's) Under Part 2 Housing Act 2004 (Stroud District Council)" (Not dated).
Is a fire risk assessment needed for the licence?
Yes, with your licence application
The council lists a written fire risk assessment as one of the documents you send with your HMO licence application.
Who can carry it out?
A "competent person"
The council says a "competent person" must carry it out. In fire safety law that means someone with enough training, experience or knowledge to assess the house properly. A careful landlord can meet that.
Which standard applies?
Local Authority Standards for Licensed Houses in Multiple Occupation (HMO's) Under Part 2 Housing Act 2004 (Stroud District Council)
Published Not dated.
Read the council's document →When did we last check?
14 October 2026
We re-check every council's documents each month and update this page when they change.
What Stroud expects in 3 typical HMOs
Worked out from the council's own fire safety rules for three common kinds of HMO. Your house may need more or less depending on its layout, which is what a fire risk assessment is for.
2-storey shared house, 5 tenants
- Fire alarm system
- Grade D2, LD3
- Fire doors on bedrooms
- Not required
- Fire door on the kitchen
- Not required
- Protected escape route
- Not required
- Heat detector in the kitchen
- Required
- Emergency lighting
- Not required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
3-storey shared house, 6 tenants
- Fire alarm system
- Grade D2, LD3
- Fire doors on bedrooms
- Required
- Fire door on the kitchen
- Required
- Protected escape route
- Required
- Heat detector in the kitchen
- Required
- Emergency lighting
- Required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
3-storey bedsits with cooking in rooms, 6 tenants
- Fire alarm system
- Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting
- Fire doors on bedrooms
- Required
- Fire door on the kitchen
- Required
- Protected escape route
- Required
- Heat detector in the kitchen
- Required
- Emergency lighting
- Required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
| Requirement | 2-storey shared house, 5 tenants | 3-storey shared house, 6 tenants | 3-storey bedsits with cooking in rooms, 6 tenants |
|---|---|---|---|
| Fire alarm system | Grade D2, LD3 | Grade D2, LD3 | Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting |
| Fire doors on bedrooms | Not required | Required | Required |
| Fire door on the kitchen | Not required | Required | Required |
| Protected escape route | Not required | Required | Required |
| Heat detector in the kitchen | Required | Required | Required |
| Emergency lighting | Not required | Required | Required |
| Fire blanket in the kitchen | Required | Required | Required |
| Fire extinguishers | Recommended | Recommended | Recommended |
- Grade D2 (mains alarms with a replaceable backup battery)
- Grade A (a panel system with call points)
- LD3 (escape route only)
- LD2 (escape route plus rooms where fires are likely to start)
In the council's own words
The wording these requirements come from, quoted from the published documents.
Fire alarms
Council's own standard
“A Category LD3 Grade A or D fire detection system conforming to BS5839: Part 6:2013 (a Grade A system will ... be required for properties occupied by 7 or more persons). The system will normally include interlinked smoke ... any cellar. Grade D detectors should have integral battery back-up. ... For 5 and 6 storey properties a Category LD2 Grade A system will be required. ... A Category LD2 Grade A or D fire detection system conforming to BS5839: Part 6:2013 (a Grade A system will ... be required for properties occupied by 7 or more persons and 3 or more storey properties). ... An additional Grade D non-interlinked smoke detector with integral battery back-up will”
Fire doors
LACORS national guide
“30-minute protected route note 8, is required, including 30-minute fire-resisting construction and FD30 doors to all risk rooms (without smoke seals ... 30-minute fire-resisting construction and FD30S doors to all risk rooms. Travel distance must not be excessive”
Escape route
LACORS national guide
“No requirement for full 30-minute protected route note 7, but the escape route should have sound, traditional construction and should not pass through risk rooms ... 30-minute protected route note 8, is required, including 30-minute fire-resisting construction”
Kitchen heat detector
LACORS national guide
“additional interlinked heat alarm with integral battery back-up located in the kitchen”
Emergency lighting
Council's own standard
“Emergency lighting (3 and 4 An emergency lighting system to BS 5266:1:2011. ... storey HMOs)”
Fire extinguishers
LACORS national guide
“a simple multi-purpose extinguisher is recommended on each floor in the common parts of HMOs and buildings containing flats.”
Spotted something out of date? Tell us and we will check it.
Common questions
Do I need a fire risk assessment for a Stroud HMO licence?
Can I do my own HMO fire risk assessment in Stroud?
Which fire safety standard does Stroud use for HMOs?
What fire alarm does a 3-storey shared house need in Stroud?
Check your Stroud HMO against the council's standard