Peterborough HMO fire safety requirements

Peterborough publishes its own HMO fire safety standard, "Fire Safety Standards in Houses in Multiple Occupations (HMOs), on the HMO standards and regulations page (Peterborough City Council)" (Page last updated 28 August 2026).

Is a fire risk assessment needed for the licence?

Yes, as a licence condition

You need a written fire risk assessment as a condition of the licence, and the council can ask to see it at any time.

Who can carry it out?

No rule on who writes it

The council does not say who must carry out the fire risk assessment, so a landlord can do it themselves, as long as it is done properly.

Which standard applies?

Fire Safety Standards in Houses in Multiple Occupations (HMOs), on the HMO standards and regulations page (Peterborough City Council)

Published Page last updated 28 August 2026.

Read the council's document →

When did we last check?

14 October 2026

We re-check every council's documents each month and update this page when they change.

What Peterborough expects in 3 typical HMOs

Worked out from the council's own fire safety rules for three common kinds of HMO. Your house may need more or less depending on its layout, which is what a fire risk assessment is for.

2-storey shared house, 5 tenants

Fire alarm system
Grade D2, LD2, plus a linked smoke alarm in each letting
Fire doors on bedrooms
Not required
Fire door on the kitchen
Required
Protected escape route
Required
Heat detector in the kitchen
Required
Emergency lighting
Not required
Fire blanket in the kitchen
Required
Fire extinguishers
Recommended

3-storey shared house, 6 tenants

Fire alarm system
Grade D2, LD2, plus a linked smoke alarm in each letting
Fire doors on bedrooms
Required
Fire door on the kitchen
Required
Protected escape route
Required
Heat detector in the kitchen
Required
Emergency lighting
Not required
Fire blanket in the kitchen
Required
Fire extinguishers
Recommended

3-storey bedsits with cooking in rooms, 6 tenants

Fire alarm system
Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting
Fire doors on bedrooms
Required
Fire door on the kitchen
Required
Protected escape route
Required
Heat detector in the kitchen
Required
Emergency lighting
Not required
Fire blanket in the kitchen
Required
Fire extinguishers
Recommended
  • Grade D2 (mains alarms with a replaceable backup battery)
  • Grade A (a panel system with call points)
  • LD2 (escape route plus rooms where fires are likely to start)

In the council's own words

The wording these requirements come from, quoted from the published documents.

Fire alarms

Council's own standard

“2 Storey Dwellings containing 3-4 persons ... Dwelling with a shared kitchen: Grade D, LD3 system with mains-powered smoke alarms with battery backup on all escape routes (hallways, landings) ... Dwelling with cooking in bedsits: Grade D, LD2 system with interlinked smoke detectors in the escape route and common areas with additional interlinked heat detectors in each bedsit and non-interlinked smoke alarms in each bedsit ... 2 Storey Dwellings containing 5+ persons ... Dwelling with a shared kitchen: Grade D, LD2 system with interlinked smoke detectors in the escape route, common areas and bedrooms + additional interlinked heat detector in each kitchen ... Dwelling with cooking in bedsits: Mixed system Grade A, LD2 system with interlinked smoke detectors in the escape route and common areas with additional heat detectors in bedsits (interlinked). Grade D mains powered smoke alarm in each bedsit (non-interlinked) ... Dwelling with a shared kitchen: Mixed system Grade A, LD2 system with interlinked smoke detectors in the escape route and in all bedrooms, kitchens and lounges and additional interlinked heat detector in each kitchen”
HMO standards and regulations (Peterborough City Council web page), Last updated 28 August 2026

Fire doors

Council's own standard

“Dwelling with cooking in bedsits: 30-minute fire doors (complete with self-closers, intumescent strips, cold smoke seals and 3x 100mm heavy duty hinges) to all risk rooms* ... Risk rooms are defined as any room which includes cooking facilities ... 30-minute fire doors (complete with self-closers, intumescent strips, cold smoke seals and 3x 100mm heavy duty hinges) to all letting rooms, common lounges and kitchens (and boiler cupboards if located on the escape route)”
HMO standards and regulations (Peterborough City Council web page), Last updated 28 August 2026

Escape route

Council's own standard

“2 Storey Dwellings containing 3-4 persons Item: Fire separation (walls/partitions/ceilings) Peterborough City Council standard: Escape routes of sound construction ... 2 Storey Dwellings containing 5+ persons Item: Fire separation (walls/partitions/ceilings) Peterborough City Council Standard: 30-minute protected escape route”
HMO standards and regulations (Peterborough City Council web page), Last updated 28 August 2026

Kitchen heat detector

LACORS national guide

“additional interlinked heat alarm with integral battery back-up located in the kitchen”
LACORS Housing - Fire Safety: guidance on fire safety provisions for certain types of existing housing, July 2008

Emergency lighting

Council's own standard

“Dwelling with cooking in bedsits: Conventional lighting (and emergency escape lighting if risk requires or there is no effective borrowed light) ... Dwelling with a shared kitchen: Conventional lighting and emergency escape lighting”
HMO standards and regulations (Peterborough City Council web page), Last updated 28 August 2026

Fire extinguishers

LACORS national guide

“a simple multi-purpose extinguisher is recommended on each floor in the common parts of HMOs and buildings containing flats.”
LACORS Housing - Fire Safety: guidance on fire safety provisions for certain types of existing housing, July 2008

Spotted something out of date? Tell us and we will check it.

Common questions

Do I need a fire risk assessment for a Peterborough HMO licence?
You need a written fire risk assessment as a condition of the licence, and the council can ask to see it at any time.
Can I do my own HMO fire risk assessment in Peterborough?
The council does not say who must carry out the fire risk assessment, so a landlord can do it themselves, as long as it is done properly.
Which fire safety standard does Peterborough use for HMOs?
Peterborough publishes "Fire Safety Standards in Houses in Multiple Occupations (HMOs), on the HMO standards and regulations page (Peterborough City Council)" (Page last updated 28 August 2026). Like most councils, it builds on the national LACORS guide.
What fire alarm does a 3-storey shared house need in Peterborough?
For a typical 3-storey shared house with 6 tenants, Peterborough's rules work out at Grade D2, LD2, plus a linked smoke alarm in each letting. Your house may need something different depending on its layout, so check it properly with a fire risk assessment.

Check your Peterborough HMO against the council's standard