North East
Northumberland HMO fire safety requirements
Northumberland publishes its own HMO fire safety standard, "Licensing of Houses in Multiple Occupation: Guidance to Applicants, Appendix 2 Fire Safety Standards (Northumberland County Council)" (Undated (about 2018)).
Is a fire risk assessment needed for the licence?
Yes, with your licence application
The council lists a written fire risk assessment as one of the documents you send with your HMO licence application.
Who can carry it out?
No rule on who writes it
The council does not say who must carry out the fire risk assessment, so a landlord can do it themselves, as long as it is done properly.
Which standard applies?
Licensing of Houses in Multiple Occupation: Guidance to Applicants, Appendix 2 Fire Safety Standards (Northumberland County Council)
Published Undated (about 2018).
Read the council's document →When did we last check?
14 October 2026
We re-check every council's documents each month and update this page when they change.
What Northumberland expects in 3 typical HMOs
Worked out from the council's own fire safety rules for three common kinds of HMO. Your house may need more or less depending on its layout, which is what a fire risk assessment is for.
2-storey shared house, 5 tenants
- Fire alarm system
- Grade D2, LD3
- Fire doors on bedrooms
- Required
- Fire door on the kitchen
- Required
- Protected escape route
- Required
- Heat detector in the kitchen
- Required
- Emergency lighting
- Not required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
3-storey shared house, 6 tenants
- Fire alarm system
- Grade D2, LD3
- Fire doors on bedrooms
- Required
- Fire door on the kitchen
- Required
- Protected escape route
- Required
- Heat detector in the kitchen
- Required
- Emergency lighting
- Not required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
3-storey bedsits with cooking in rooms, 6 tenants
- Fire alarm system
- Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting
- Fire doors on bedrooms
- Required
- Fire door on the kitchen
- Required
- Protected escape route
- Required
- Heat detector in the kitchen
- Required
- Emergency lighting
- Required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
| Requirement | 2-storey shared house, 5 tenants | 3-storey shared house, 6 tenants | 3-storey bedsits with cooking in rooms, 6 tenants |
|---|---|---|---|
| Fire alarm system | Grade D2, LD3 | Grade D2, LD3 | Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting |
| Fire doors on bedrooms | Required | Required | Required |
| Fire door on the kitchen | Required | Required | Required |
| Protected escape route | Required | Required | Required |
| Heat detector in the kitchen | Required | Required | Required |
| Emergency lighting | Not required | Not required | Required |
| Fire blanket in the kitchen | Required | Required | Required |
| Fire extinguishers | Recommended | Recommended | Recommended |
- Grade D2 (mains alarms with a replaceable backup battery)
- Grade A (a panel system with call points)
- LD3 (escape route only)
- LD2 (escape route plus rooms where fires are likely to start)
In the council's own words
The wording these requirements come from, quoted from the published documents.
Fire alarms
Council's own standard
“Benchmark guidance for recommended fire safety standards in bedsit HMO”
Fire doors
Council's own standard
“Benchmark guidance for recommended fire safety standards in shared houses up to 3 storeys ... No requirement for protected route ... No requirement for fire doors”
Escape route
Council's own standard
“Benchmark guidance for recommended fire safety standards in shared houses up to 3 storeys ... No requirement for protected route ... No requirement for fire doors”
Kitchen heat detector
LACORS national guide
“additional interlinked heat alarm with integral battery back-up located in the kitchen”
Emergency lighting
Council's own standard
“Emergency escape lighting required Conventional artificial lighting required ... No requirement for emergency escape lighting ... Emergency escape lighting required only if the route is long or complex or where there is no effective borrowed”
Fire extinguishers
LACORS national guide
“a simple multi-purpose extinguisher is recommended on each floor in the common parts of HMOs and buildings containing flats.”
Spotted something out of date? Tell us and we will check it.
Not in Northumberland?
Common questions
Do I need a fire risk assessment for a Northumberland HMO licence?
Can I do my own HMO fire risk assessment in Northumberland?
Which fire safety standard does Northumberland use for HMOs?
What fire alarm does a 3-storey shared house need in Northumberland?
Check your Northumberland HMO against the council's standard
Answer plain-English questions about your house and get a fire risk assessment report built on Northumberland's rules. £45, no subscription.