Kensington and Chelsea HMO fire safety requirements

Kensington and Chelsea publishes its own HMO fire safety standard, "Houses in multiple occupation: Guide to Flats in Multiple Occupation and Shared Houses (Royal Borough of Kensington and Chelsea)" (Version 1, 1 August 2011).

Is a fire risk assessment needed for the licence?

Expected, but not sent in

The council's guidance talks about fire risk assessments, but it does not ask you to send one with your application. Fire safety law still says you need one.

Who can carry it out?

No rule on who writes it

The council does not say who must carry out the fire risk assessment, so a landlord can do it themselves, as long as it is done properly.

Which standard applies?

Houses in multiple occupation: Guide to Flats in Multiple Occupation and Shared Houses (Royal Borough of Kensington and Chelsea)

Published Version 1, 1 August 2011.

Read the council's document →

When did we last check?

14 October 2026

We re-check every council's documents each month and update this page when they change.

What Kensington and Chelsea expects in 3 typical HMOs

Worked out from the council's own fire safety rules for three common kinds of HMO. Your house may need more or less depending on its layout, which is what a fire risk assessment is for.

2-storey shared house, 5 tenants

Fire alarm system
Grade D2, LD3
Fire doors on bedrooms
Required
Fire door on the kitchen
Required
Protected escape route
Required
Heat detector in the kitchen
Required
Emergency lighting
Required
Fire blanket in the kitchen
Required
Fire extinguishers
Required

3-storey shared house, 6 tenants

Fire alarm system
Grade D2, LD3
Fire doors on bedrooms
Required
Fire door on the kitchen
Required
Protected escape route
Required
Heat detector in the kitchen
Required
Emergency lighting
Required
Fire blanket in the kitchen
Required
Fire extinguishers
Required

3-storey bedsits with cooking in rooms, 6 tenants

Fire alarm system
Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting
Fire doors on bedrooms
Required
Fire door on the kitchen
Required
Protected escape route
Required
Heat detector in the kitchen
Required
Emergency lighting
Required
Fire blanket in the kitchen
Required
Fire extinguishers
Required
  • Grade D2 (mains alarms with a replaceable backup battery)
  • Grade A (a panel system with call points)
  • LD3 (escape route only)
  • LD2 (escape route plus rooms where fires are likely to start)

In the council's own words

The wording these requirements come from, quoted from the published documents.

Fire alarms

LACORS national guide

“Shared house HMO of three or four storeys (shared cooking facilities) Grade D: LD3 coverage + additional detection to the kitchen, lounge and any cellar containing a risk (interlinked) Shared house HMO of five or six storeys (shared cooking facilities) Grade A: LD2 coverage ... Bedsit HMO of one or two storeys with individual cooking facilities within bedsits A mixed system: Grade D: LD2 coverage in the common areas and heat detectors in bedsits (interlinked) Grade D smoke alarm in each bedsit to protect the sleeping occupants (non-interlinked) Bedsit HMO of three to six storeys with individual cooking facilities within bedsits A mixed system: Grade A: LD2 coverage in the common areas ... Where cooking facilities are sited in shared kitchen, not within bedsits: interlinked smoke alarms with integral battery backup located in each bedsit”
LACORS Housing - Fire Safety: guidance on fire safety provisions for certain types of existing housing, July 2008

Fire doors

Council's own standard

“In general terms the following fire safety measures must be considered: ... 30 minute fire resistant doors are required on all doors opening onto the protected route.”
Houses in multiple occupation: Guide to Flats in Multiple Occupation and Shared Houses (Royal Borough of Kensington and Chelsea), Version 1, 1 August 2011

Escape route

Council's own standard

“Provision of a protected escape route The protected escape route leads from the letting to the street exit through the building, and normally includes staircases, passageways, landings and protected lobbies. Protection is provided by fire resistant doors and partitions.”
Houses in multiple occupation: Guide to Flats in Multiple Occupation and Shared Houses (Royal Borough of Kensington and Chelsea), Version 1, 1 August 2011

Kitchen heat detector

LACORS national guide

“additional interlinked heat alarm with integral battery back-up located in the kitchen”
LACORS Housing - Fire Safety: guidance on fire safety provisions for certain types of existing housing, July 2008

Emergency lighting

Council's own standard

“Emergency lighting which comes on if mains electricity fails must be fitted to illuminate the protected route and some internal staircases.”
Houses in multiple occupation: Guide to Flats in Multiple Occupation and Shared Houses (Royal Borough of Kensington and Chelsea), Version 1, 1 August 2011

Fire extinguishers

Council's own standard

“Fire extinguishers, rated 13A (for example, nine litre water type extinguishers) must be provided within the common parts, normally one per landing”
Houses in multiple occupation: Guide to Flats in Multiple Occupation and Shared Houses (Royal Borough of Kensington and Chelsea), Version 1, 1 August 2011

Spotted something out of date? Tell us and we will check it.

Not in Kensington and Chelsea?

Common questions

Do I need a fire risk assessment for a Kensington and Chelsea HMO licence?
The council's guidance talks about fire risk assessments, but it does not ask you to send one with your application. Fire safety law still says you need one.
Can I do my own HMO fire risk assessment in Kensington and Chelsea?
The council does not say who must carry out the fire risk assessment, so a landlord can do it themselves, as long as it is done properly.
Which fire safety standard does Kensington and Chelsea use for HMOs?
Kensington and Chelsea publishes "Houses in multiple occupation: Guide to Flats in Multiple Occupation and Shared Houses (Royal Borough of Kensington and Chelsea)" (Version 1, 1 August 2011). Like most councils, it builds on the national LACORS guide.
What fire alarm does a 3-storey shared house need in Kensington and Chelsea?
For a typical 3-storey shared house with 6 tenants, Kensington and Chelsea's rules work out at Grade D2, LD3. Your house may need something different depending on its layout, so check it properly with a fire risk assessment.