East Hertfordshire HMO fire safety requirements

East Hertfordshire publishes its own HMO fire safety standard, "Houses in Multiple Occupation (HMO): advice and guidance to landlords, managing agents and tenants (Guide to HMOs)" (2018). It is based on the Hertfordshire standard, which 1 other council uses too.

Is a fire risk assessment needed for the licence?

Not stated by the council

We could not find the council saying whether it wants to see your fire risk assessment. Fire safety law still says the landlord of an HMO must have one.

Who can carry it out?

No rule on who writes it

The council does not say who must carry out the fire risk assessment, so a landlord can do it themselves, as long as it is done properly.

Which standard applies?

Houses in Multiple Occupation (HMO): advice and guidance to landlords, managing agents and tenants (Guide to HMOs)

Published 2018.

Read the council's document →

When did we last check?

29 September 2026

We re-check every council's documents each month and update this page when they change.

What East Hertfordshire expects in 3 typical HMOs

Worked out from the council's own fire safety rules for three common kinds of HMO. Your house may need more or less depending on its layout, which is what a fire risk assessment is for.

2-storey shared house, 5 tenants

Fire alarm system
Grade D2, LD2, plus a linked smoke alarm in each letting
Fire doors on bedrooms
Required
Fire door on the kitchen
Required
Protected escape route
Required
Heat detector in the kitchen
Required
Emergency lighting
Not required
Fire blanket in the kitchen
Required
Fire extinguishers
Not required

3-storey shared house, 6 tenants

Fire alarm system
Grade A, LD2, plus a linked smoke alarm in each letting
Fire doors on bedrooms
Required
Fire door on the kitchen
Required
Protected escape route
Required
Heat detector in the kitchen
Required
Emergency lighting
Not required
Fire blanket in the kitchen
Required
Fire extinguishers
Not required

3-storey bedsits with cooking in rooms, 6 tenants

Fire alarm system
Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting
Fire doors on bedrooms
Required
Fire door on the kitchen
Required
Protected escape route
Required
Heat detector in the kitchen
Required
Emergency lighting
Not required
Fire blanket in the kitchen
Required
Fire extinguishers
Not required
  • Grade D2 (mains alarms with a replaceable backup battery)
  • Grade A (a panel system with call points)
  • LD2 (escape route plus rooms where fires are likely to start)

In the council's own words

The wording these requirements come from, quoted from the published documents.

Fire alarms

Shared regional standard

“PLAN 1: A system of mains powered ... detectors to form a Grade D LD2 system ... route. lnterlinked smoke alarms with ... integral battery back-up in each bedroom ... lnterlinked heat alarms with integral ... battery back-up in each bedroom ... containing cooking facilities ... Additional non-interlinked smoke alarms with ... integral battery back-up in each bedroom ... detectors to form a Grade A LD2 system in ... PLAN 2: Typical two storey ... PLAN 3: Typical three storey”
Houses in Multiple Occupation (HMO): free advice and guidance (Dacorum Borough Council fire safety leaflet), 2018

Fire doors

Shared regional standard

“A fire door of at least ... 30 minute fire resistance, with cold smoke ... seals, intumescent strips and self-closers, ... must be installed in each doorway leading ... onto the escape route, except bathrooms”
Houses in Multiple Occupation (HMO): free advice and guidance (Dacorum Borough Council fire safety leaflet), 2018

Escape route

Shared regional standard

“least 30 minute fire resistance should be ... provided to the route as indicated by red on”
Houses in Multiple Occupation (HMO): free advice and guidance (Dacorum Borough Council fire safety leaflet), 2018

Kitchen heat detector

LACORS national guide

“additional interlinked heat alarm with integral battery back-up located in the kitchen”
LACORS Housing - Fire Safety: guidance on fire safety provisions for certain types of existing housing, July 2008

Emergency lighting

LACORS national guide

“Emergency escape lighting required only if the route is long or complex or where there is no effective borrowed light ... Shared house HMO of five or six storeys (shared cooking facilities) Conventional lighting and emergency escape lighting”
LACORS Housing - Fire Safety: guidance on fire safety provisions for certain types of existing housing, July 2008

Fire extinguishers

Shared regional standard

“Although not a requirement, where your risk assessment indicates that fire extinguishers are required, they shall be multipurpose extinguishers”
Houses in Multiple Occupation (HMO): free advice and guidance (Dacorum Borough Council fire safety leaflet), 2018

Spotted something out of date? Tell us and we will check it.

Not in East Hertfordshire?

Councils using the same standard as East Hertfordshire

Common questions

Do I need a fire risk assessment for a East Hertfordshire HMO licence?
We could not find the council saying whether it wants to see your fire risk assessment. Fire safety law still says the landlord of an HMO must have one.
Can I do my own HMO fire risk assessment in East Hertfordshire?
The council does not say who must carry out the fire risk assessment, so a landlord can do it themselves, as long as it is done properly.
Which fire safety standard does East Hertfordshire use for HMOs?
East Hertfordshire publishes "Houses in Multiple Occupation (HMO): advice and guidance to landlords, managing agents and tenants (Guide to HMOs)" (2018).
What fire alarm does a 3-storey shared house need in East Hertfordshire?
For a typical 3-storey shared house with 6 tenants, East Hertfordshire's rules work out at Grade A, LD2, plus a linked smoke alarm in each letting. Your house may need something different depending on its layout, so check it properly with a fire risk assessment.