Yorkshire and The Humber
Calderdale HMO fire safety requirements
Calderdale publishes its own HMO fire safety standard, "Calderdale Council Standards for Houses in Multiple Occupation" (Revised November 2023).
Is a fire risk assessment needed for the licence?
Yes, with your licence application
The council lists a written fire risk assessment as one of the documents you send with your HMO licence application.
Who can carry it out?
A "competent person"
The council says a "competent person" must carry it out. In fire safety law that means someone with enough training, experience or knowledge to assess the house properly. A careful landlord can meet that.
Which standard applies?
Calderdale Council Standards for Houses in Multiple Occupation
Published Revised November 2023.
Read the council's document →When did we last check?
15 October 2026
We re-check every council's documents each month and update this page when they change.
What Calderdale expects in 3 typical HMOs
Worked out from the council's own fire safety rules for three common kinds of HMO. Your house may need more or less depending on its layout, which is what a fire risk assessment is for.
2-storey shared house, 5 tenants
- Fire alarm system
- Grade D2, LD1
- Fire doors on bedrooms
- Required
- Fire door on the kitchen
- Required
- Protected escape route
- Not required
- Heat detector in the kitchen
- Required
- Emergency lighting
- Required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
3-storey shared house, 6 tenants
- Fire alarm system
- Grade D2, LD1
- Fire doors on bedrooms
- Required
- Fire door on the kitchen
- Required
- Protected escape route
- Required
- Heat detector in the kitchen
- Required
- Emergency lighting
- Required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
3-storey bedsits with cooking in rooms, 6 tenants
- Fire alarm system
- Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting
- Fire doors on bedrooms
- Required
- Fire door on the kitchen
- Required
- Protected escape route
- Required
- Heat detector in the kitchen
- Required
- Emergency lighting
- Required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
| Requirement | 2-storey shared house, 5 tenants | 3-storey shared house, 6 tenants | 3-storey bedsits with cooking in rooms, 6 tenants |
|---|---|---|---|
| Fire alarm system | Grade D2, LD1 | Grade D2, LD1 | Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting |
| Fire doors on bedrooms | Required | Required | Required |
| Fire door on the kitchen | Required | Required | Required |
| Protected escape route | Not required | Required | Required |
| Heat detector in the kitchen | Required | Required | Required |
| Emergency lighting | Required | Required | Required |
| Fire blanket in the kitchen | Required | Required | Required |
| Fire extinguishers | Recommended | Recommended | Recommended |
- Grade D2 (mains alarms with a replaceable backup battery)
- Grade A (a panel system with call points)
- LD1 (alarms in all rooms and on the escape route)
- LD2 (escape route plus rooms where fires are likely to start)
In the council's own words
The wording these requirements come from, quoted from the published documents.
Fire alarms
Council's own standard
“In most cases a fire detection and alarm system that complies with BS5839 Part 6: 2019 is required.”
Fire doors
Council's own standard
“Generally, all rooms opening on to an escape route should be provided with a 30(s) minute fire door”
Escape route
LACORS national guide
“No requirement for full 30-minute protected route note 7, but the escape route should have sound, traditional construction and should not pass through risk rooms ... 30-minute protected route note 8, is required, including 30-minute fire-resisting construction”
Kitchen heat detector
LACORS national guide
“additional interlinked heat alarm with integral battery back-up located in the kitchen”
Emergency lighting
Council's own standard
“An emergency lighting system shall be provided in most cases with luminaires provided in such numbers and locations to adequately illuminate the staircase enclosure”
Fire extinguishers
LACORS national guide
“a simple multi-purpose extinguisher is recommended on each floor in the common parts of HMOs and buildings containing flats.”
Spotted something out of date? Tell us and we will check it.
Common questions
Do I need a fire risk assessment for a Calderdale HMO licence?
Can I do my own HMO fire risk assessment in Calderdale?
Which fire safety standard does Calderdale use for HMOs?
What fire alarm does a 3-storey shared house need in Calderdale?
Check your Calderdale HMO against the council's standard
Answer plain-English questions about your house and get a fire risk assessment report built on Calderdale's rules. £45, no subscription.