Bury HMO fire safety requirements
Bury publishes its own HMO fire safety standard, "Houses in Multiple Occupation: Guidance for landlords (Bury Council)" (February 2026).
Is a fire risk assessment needed for the licence?
Yes, with your licence application
The council lists a written fire risk assessment as one of the documents you send with your HMO licence application.
Who can carry it out?
No rule on who writes it
The council does not say who must carry out the fire risk assessment, so a landlord can do it themselves, as long as it is done properly.
Which standard applies?
Houses in Multiple Occupation: Guidance for landlords (Bury Council)
Published February 2026.
Read the council's document →When did we last check?
17 October 2026
We re-check every council's documents each month and update this page when they change.
What Bury expects in 3 typical HMOs
Worked out from the council's own fire safety rules for three common kinds of HMO. Your house may need more or less depending on its layout, which is what a fire risk assessment is for.
2-storey shared house, 5 tenants
- Fire alarm system
- Grade D2, LD3
- Fire doors on bedrooms
- Required
- Fire door on the kitchen
- Required
- Protected escape route
- Required
- Heat detector in the kitchen
- Required
- Emergency lighting
- Not required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
3-storey shared house, 6 tenants
- Fire alarm system
- Grade D2, LD3
- Fire doors on bedrooms
- Required
- Fire door on the kitchen
- Required
- Protected escape route
- Required
- Heat detector in the kitchen
- Required
- Emergency lighting
- Required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
3-storey bedsits with cooking in rooms, 6 tenants
- Fire alarm system
- Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting
- Fire doors on bedrooms
- Required
- Fire door on the kitchen
- Required
- Protected escape route
- Required
- Heat detector in the kitchen
- Required
- Emergency lighting
- Required
- Fire blanket in the kitchen
- Required
- Fire extinguishers
- Recommended
| Requirement | 2-storey shared house, 5 tenants | 3-storey shared house, 6 tenants | 3-storey bedsits with cooking in rooms, 6 tenants |
|---|---|---|---|
| Fire alarm system | Grade D2, LD3 | Grade D2, LD3 | Grade A, LD2, plus a linked heat detector and a standalone smoke alarm in each letting |
| Fire doors on bedrooms | Required | Required | Required |
| Fire door on the kitchen | Required | Required | Required |
| Protected escape route | Required | Required | Required |
| Heat detector in the kitchen | Required | Required | Required |
| Emergency lighting | Not required | Required | Required |
| Fire blanket in the kitchen | Required | Required | Required |
| Fire extinguishers | Recommended | Recommended | Recommended |
- Grade D2 (mains alarms with a replaceable backup battery)
- Grade A (a panel system with call points)
- LD3 (escape route only)
- LD2 (escape route plus rooms where fires are likely to start)
In the council's own words
The wording these requirements come from, quoted from the published documents.
Fire alarms
LACORS national guide
“Shared house HMO of three or four storeys (shared cooking facilities) Grade D: LD3 coverage + additional detection to the kitchen, lounge and any cellar containing a risk (interlinked) Shared house HMO of five or six storeys (shared cooking facilities) Grade A: LD2 coverage ... Bedsit HMO of one or two storeys with individual cooking facilities within bedsits A mixed system: Grade D: LD2 coverage in the common areas and heat detectors in bedsits (interlinked) Grade D smoke alarm in each bedsit to protect the sleeping occupants (non-interlinked) Bedsit HMO of three to six storeys with individual cooking facilities within bedsits A mixed system: Grade A: LD2 coverage in the common areas ... Where cooking facilities are sited in shared kitchen, not within bedsits: interlinked smoke alarms with integral battery backup located in each bedsit”
Fire doors
Council's own standard
“Provide a means of escape so that:- ... Doors within the escape route shall be of the same standard (FD30S/ E30Sa) unless the door is to a bathroom or WC that contains no fire risk.”
Escape route
Council's own standard
“Provide a means of escape so that:- 1. The staircase enclosure forms a protected route, from the topmost floor to ground level. 2. All walls, screens and partitions forming the staircase enclosure to provide 30 minutes fire resistance.”
Kitchen heat detector
LACORS national guide
“additional interlinked heat alarm with integral battery back-up located in the kitchen”
Emergency lighting
Council's own standard
“HMO of up to two storeys Conventional lighting HMO of three or more storeys Conventional lighting and Emergency escape lighting”
Fire extinguishers
LACORS national guide
“a simple multi-purpose extinguisher is recommended on each floor in the common parts of HMOs and buildings containing flats.”
Spotted something out of date? Tell us and we will check it.
Common questions
Do I need a fire risk assessment for a Bury HMO licence?
Can I do my own HMO fire risk assessment in Bury?
Which fire safety standard does Bury use for HMOs?
What fire alarm does a 3-storey shared house need in Bury?
Check your Bury HMO against the council's standard
Answer plain-English questions about your house and get a fire risk assessment report built on Bury's rules. £45, no subscription.