Emergency Lighting Requirements for Commercial Premises (BS 5266)

Missing emergency lighting can trigger a prohibition notice under the RRO 2005. Here is what BS 5266 requires for testing frequency, duration and design.

Bradley, Founder of FRASafe
BradleyFounder, FRASafe
7 min read

Lose power during a fire evacuation with no emergency lighting fitted, and the first thing an investigator checks afterwards is whether your fire risk assessment even considered it, because missing emergency lighting is one of the fastest routes from a routine fire safety inspection to a prohibition notice or a personal prosecution of the responsible person. It is also one of the cheapest fixes on this list, which is exactly why enforcement officers have little patience for finding it missing.

Ready to get compliant?

Start Your Small Business Fire Risk Assessment

FRASafe walks you through an assessment aligned with PAS 79-1:2020 for your office or workplace. £45 for the PDF report.

How our small business fire risk assessment works →
Start Your Assessment

No account needed to start

Who the duty falls on

Under the Regulatory Reform (Fire Safety) Order 2005 (RRO 2005), the responsible person, normally the employer, or whoever has control of the premises, must ensure that escape routes requiring illumination are provided with emergency lighting of adequate intensity if normal lighting fails. This sits alongside the duty to carry out a fire risk assessment under Article 9, and since 1 October 2023, section 156 of the Building Safety Act 2022 requires that assessment to be recorded in writing whatever the size of the business. The old exemption for premises with fewer than five employees no longer applies, so a two-person office has exactly the same written assessment duty as a 200-person warehouse.

The duty is not just "have some emergency lights." It is to assess, room by room and route by route, where normal lighting failure would leave people unable to find their way out, and to fit lighting that answers that specific risk. A single corridor with a window and daylight at 3pm may need less than the same corridor used on a winter evening shift, which is why the assessment drives the specification rather than a generic parts list.

What BS 5266 actually specifies

BS 5266-1 is the UK code of practice for the design, installation and maintenance of emergency lighting in non-domestic premises, and it is the standard most fire risk assessors and electricians work to when specifying a system. It sets out where luminaires are needed (over fire exits, at changes of floor level, at each exit sign, near fire-fighting equipment and alarm call points, and along escape routes generally) and the minimum light levels those luminaires must provide so that people can see to move safely.

Two further standards sit alongside it in practice: BS EN 50172 (also published as BS 5266-8) covers the emergency escape lighting system itself and the testing regime, and BS 5266-8 is frequently the reference point councils and fire officers cite when checking testing records on an inspection. None of these documents are law in themselves, but a fire risk assessor who departs from them without a documented reason is taking on risk they would struggle to defend if something went wrong.

Non-maintained vs maintained systems

A non-maintained emergency light only comes on when the mains supply fails, which suits most workplaces that are occupied during normal lighting hours and simply need backup if the power drops. A maintained system stays lit continuously, on mains power normally and on battery during a cut, which matters in premises like cinemas, theatres and some retail units where lighting is already dimmed or used for effect and occupants need to see exit routes at all times, not just during a power failure.

Most offices, shops, warehouses and small business premises use non-maintained systems. The fire risk assessment should state which type has been specified and why, because a mismatch (a maintained system fitted where non-maintained would do, or vice versa) is a flag that the assessment was not properly tailored to the building.

Self-contained luminaires or a central battery system

Most small and medium premises use self-contained luminaires, where each light has its own battery built in, charges from the local mains circuit and switches itself on when that circuit loses power. They are cheap to install and simple to add to as a building changes, which is why they dominate shops, offices and small warehouses.

Larger or more complex sites sometimes use a central battery system instead, where one battery bank in a plant room feeds every emergency luminaire in the building through dedicated wiring. That approach costs more to install but makes testing and battery replacement far simpler, since there is one battery set to maintain rather than dozens scattered through the building. Either approach can meet BS 5266-1, and the fire risk assessment should record which one is in place and why it suits the building, rather than leaving a visiting officer to guess.

Free tool

How fire-safe is your workplace?

Take the free 60-second check and get an instant Red, Amber or Green score, plus the things to fix first.

Take the free check

Testing and the records you need to keep

The standard testing regime splits into two intervals. A monthly function test involves a short simulated mains failure, typically using a secure test switch or key rather than isolating the whole circuit, lasting long enough to confirm every luminaire comes on, batteries hold charge and there is no visible damage. This should take a matter of minutes per circuit and gets logged in a fire safety log book with the date, who carried it out, and any defects found.

Once a year, the system needs a full duration test: the mains supply to the lighting circuit is switched off and the emergency lighting left running for its full rated duration, normally three hours, to confirm the batteries genuinely hold enough charge to light the building for as long as the specification claims. This is more disruptive to run (you cannot do it during trading hours in most retail or office settings) and is usually carried out by a competent electrical contractor who issues a certificate afterwards. Keep that certificate: insurers ask for it after a fire claim, and inspectors ask for it during a routine visit, often before they ask for anything else.

A gap in the testing log is treated the same as a system that does not work at all, because there is no way to prove otherwise. If you cannot find a testing record for the previous twelve months, do not wait for an inspection to find that out. The same discipline applies to fire door inspections, where a missing record creates exactly the same enforcement exposure even if the doors themselves are fine.

Where businesses most often get caught out

Extensions and refurbishments are the most common gap. A business fits emergency lighting when it first occupies a unit, then extends into an adjoining unit or reconfigures the floor plan years later, and nobody revisits the lighting scheme to check the new layout is still covered. An exit that used to be close to a luminaire can end up metres away from any emergency light once a partition wall moves, and nothing about that change shows up unless someone actually walks the new route and checks it against BS 5266-1.

The other common failure is treating emergency lighting as a one-off installation rather than a maintained system. Batteries degrade over years of monthly discharge cycles, and a luminaire that passed its monthly test eighteen months ago can fail the three-hour annual test today simply because the battery is near the end of its service life. That is precisely why the annual full-duration test exists, and why it needs a competent person rather than a quick visual check. For the wider testing obligations that sit alongside emergency lighting, see how often a fire marshal needs refresher training and how that interacts with the evacuation plan your lighting is meant to support.

Next steps

Emergency lighting is one of the few fire safety measures that is almost invisible until the one moment it matters most, which is exactly why it gets neglected and exactly why inspectors check it first. Walk your premises during a staged power-off test if you have not done one recently, confirm every escape route luminaire still lights to the correct duration, and make sure your fire-fighting equipment and signage are reflected in the same written assessment as your lighting scheme.

FRASafe's small business fire risk assessment walks you through every area the RRO 2005 requires, including emergency lighting coverage and testing records, completed online in 30 to 45 minutes for £45.